Sizing K2 and K3 radiators for 40 °C flow

Radiator catalogues rate output at Delta T 50 K (75 °C boiler flow). Running the same panel at 45 °C flow / 40 °C return (Delta T 22.5 K in a 20 °C room) cuts its heat output to roughly 36% of the brochure number, so installers specify larger K2 double or K3 triple convectors.

Why radiator brochure wattage drops by more than half on a heat pump, EN 442 output factors, K1 vs K2 vs K3 panels and pipe diameter rules.

Free, no obligation. One local installer prices it, not five.

  • 5 °Cheat pump flow-to-return Delta T
  • ~0.36×output factor at 45 °C vs 75 °C
  • €100–€250K2 panel supply cost
  • €180–€400K3 triple convector supply
A white steel panel convector radiator fitted on an interior painted wall

EN 442 output factors at low water temperatures

Standard European radiator testing (EN 442) publishes wattage at Delta T 50 K (75 °C flow, 65 °C return, 20 °C room). Lowering water flow temperature for a heat pump reduces the mean temperature difference between the steel panel and room air dramatically:

75 / 65 °C1.00×Old boiler ΔT 50 K
55 / 50 °C0.56×High-flow HP ΔT 32.5 K
45 / 40 °C0.36×Target HP ΔT 22.5 K
40 / 35 °C0.26×Ultra-low ΔT 17.5 K

Practical example: a living room with a measured −3 °C heat loss of 1,400 W needs a radiator rated at roughly 3,900 W (EN 442 Delta T 50 K) to keep the room at 20 °C using 45 °C flow water (3,900 W × 0.36 = 1,404 W). A single 600 × 1,600 mm K3 triple convector or two 600 × 1,200 mm K2 doubles hits that easily.

Price my air-to-water system

Four quick taps and you see the full cost and net after the €6,500 SEAI grant before any phone number is asked for. One local installer rings you, not five.

Older pre-2000 house (8 to 14 kW), radiators (with K2/K3 swaps), SEAI grant: €14,800 to €22,000 full (€8,300 to €15,500 after €6,500 grant).

Step 1 of 5

What kind of house is it?

Pick the closest match. The installer checks room heat loss on site.

How the price is worked out

The range reflects typical Irish supply-and-install air-to-water hydronic heat pump packages at 9% VAT: outdoor monobloc or split unit, indoor controls, a 200 L to 300 L heat-pump hot water cylinder, core pipework, emitter allowance and commissioning. Where SEAI grant applies to a pre-2021 house, we deduct the €6,500 base Heat Pump System grant to give a conservative net figure; qualifying oil or gas boiler swaps can also claim up to €2,000 for central heating upgrades and a €4,000 Renewable Heat Bonus under SEAI rules. Attic or wall insulation upgrades, ESB 16 kVA supply upgrades (€2,245) and floor screed are separate. airtowaterheating.ie is not SEAI or a government body and does not award grants. Only a room-by-room heat-loss survey gives a firm quote.

Comparing K1, K2 and K3 panels plus pipework rules

K1 (Type 11, single panel + 1 fin)

Depth off wall
~65 mm
Output vs K1 (same width)
1.0× baseline
Typical use in Irish retrofits
Rarely big enough on heat pumps except small box bedrooms.

K2 (Type 22, double panel + 2 fins)

Depth off wall
~105 mm
Output vs K1 (same width)
1.7× to 1.9× output
Typical use in Irish retrofits
Standard workhorse across bedrooms, kitchens and hallways.

K3 (Type 33, triple panel + 3 fins)

Depth off wall
~160 mm
Output vs K1 (same width)
2.4× to 2.6× output
Typical use in Irish retrofits
High-loss living rooms or short wall spaces under bay windows.

Fan-assisted low-temp convector

Depth off wall
~130 mm
Output vs K1 (same width)
3.0×+ output
Typical use in Irish retrofits
Tight alcoves where wall width is strictly limited.
  • Higher water flow rate needs open pipes. Because a heat pump moves water across a 5 °C drop instead of a boiler's 20 °C drop, it circulates roughly four times more litres per minute. Main spine runs should be 22 mm or 28 mm, with 15 mm drops to individual rads.
  • Lockshield balancing is mandatory. SEAI DTSS v4.0 requires every radiator to be balanced so the farthest bedroom warms evenly without short-circuiting flow through the nearest hall radiator.
  • Existing valve centre spacing. Swapping a K1 to a K2 or K3 shifts the valve centres slightly farther from the wall, which a plumber adjusts neatly with offset tails or elbow extensions.

Common questions before switching

Do K3 triple radiators stick out too far into the room?

A K3 panel sits roughly 160 mm off the finished wall (plus brackets). Under a window sill or in a sitting room alcove they blend cleanly; in narrow corridors a longer K2 panel keeps walkway width clearer.

Are aluminium radiators better than steel K2/K3 panels for heat pumps?

Aluminium heats up slightly faster per litre of water, though total room heat output still depends strictly on certified EN 442 surface output at low Delta T. Quality steel K2/K3 convectors usually give more watts per euro.

Can microbore 8 mm or 10 mm copper pipes run an air-to-water heat pump?

Often not without noise or flow-rate restrictions on larger rooms. Many installers re-pipe key ground-floor zones in 15 mm and 22 mm during an older retrofit.

How much does upgrading six radiators add to an install?

At €280 to €550 supplied and fitted per swap, upgrading six panels adds roughly €1,700 to €3,000, eligible for up to €2,000 under SEAI's central heating grant on qualifying pre-2021 homes.

All air-to-water heating pages and guides

An outdoor air-to-water heat pump unit on a plinth beside a red-brick wall and garden shrubs

See your air-to-water price before anyone rings

Pick your house size, radiators or underfloor heating and SEAI grant route. When you want a room-by-room heat-loss quote, your outline goes to a single local heating installer in your county.